IG01 System Technical Data:
Fire extinguishing agent: 100%Ar
Minimum working pressure at 0℃: 14.0MPa
Maximum working pressure at 50℃: 16.5MPa
Gas filling density: 259.22kg/m3
Cylinder volume: 90L
Working temperature: 0~50℃
Storage pressure: 15MPa
Working voltage: DC24V
Discharge lasting time: ≤60s
Argon comes from the air and comes back to the air after putting out the fire. Both the GWP and the ODP are 0; it means IG01 system will never do damage to ozone layer, and will never bring about greenhouse effect, environment friendly. Argon does not have any chemical reaction with other materials, and sticks to its own chemical properties, no secondary pollution.
The principle to putting out the fire for IG01 system is to reduce the oxygen concentration from 20.9% to 15% below. When the oxygen concentration is less than 15%, the fire will be put out. So IG01 system is a total flooding system.
There are three ways to activate the IG01 system: automatic activation, manual activation and emergency activation. Fire detectors send signals to control panel; control panel starts the solenoid valve and cylinder valves; agent will be discharged. No vaporization will happen during the agent discharge; the temperature in the protection area will not decrease, no damage to equipment, instruments and documents.
|